In short
- Deflection limits protect finishes, ceilings, partitions and the feeling of the floor — they are serviceability checks, made with unfactored loads.
- Typical limits: span/360 under live load and span/240 under total load for floors; span/250 and span/500 in the Eurocodes for concrete.
- Deflection grows with the fourth power of the span and falls with the moment of inertia, so a small change in span or depth makes a large difference.
Why a limit is written as span/n
A strength check asks whether the beam can carry the load without failing. A deflection check asks whether the beam bends so much that something attached to it is damaged or that people notice. A plaster ceiling cracks long before the beam above it is overstressed; a door frame under a sagging lintel jams; a long, flexible floor feels soft underfoot.
Because the damage depends on the curvature of the member rather than on the absolute movement, limits are expressed as a fraction of the span: span/360 means that a 6 m beam may deflect 16.7 mm and a 9 m beam 25 mm. The ratio keeps the curvature roughly the same for long and short spans.
Typical limits
The values below are the ones most often met in practice. Always use the code and the national annex that apply to your project; they include footnotes and exceptions that a summary cannot show.
| Member and code | Load considered | Limit |
|---|---|---|
| Floor members — IBC Table 1604.3 | Live load | L/360 |
| Floor members — IBC Table 1604.3 | Dead + live load | L/240 |
| Roof members supporting a plaster or stucco ceiling — IBC | Live, snow or wind load | L/360 |
| Roof members supporting a non-plaster ceiling — IBC | Live, snow or wind load | L/240 |
| Roof members not supporting a ceiling — IBC | Live, snow or wind load | L/180 |
| Concrete beams and slabs — EN 1992-1-1, 7.4.1 | Quasi-permanent load, total sag | L/250 |
| Concrete beams and slabs — EN 1992-1-1, 7.4.1 | Deflection after construction, with damageable finishes | L/500 |
| Timber beams — EN 1995-1-1, Table 7.2 | Instantaneous deflection | L/300 to L/500 |
For a cantilever, most codes measure the limit against twice the cantilever length, because a cantilever of length a bends like half of a simple beam of span 2a.
Which load goes with which limit
The live-load limit is the stricter ratio but it is applied only to the part of the deflection caused by live load: finishes are usually installed after the self-weight has already deflected the beam, so they only see what comes later. The total-load limit covers the whole deflection, including the dead load, and is mostly about appearance and drainage.
Concrete and timber keep deflecting under sustained load because of creep. Codes account for it with an extra long-term deflection under the sustained part of the load — in ACI 318 the immediate deflection times ξ/(1 + 50ρ′), with ξ = 2 for loads held five years or more; in the Eurocodes an effective modulus for concrete and the factor kdef for timber. A check made with the short-term modulus alone underestimates the final sag of these materials.
Maximum deflection of common beam cases
For a prismatic, linear-elastic beam the maximum deflection can be written as a coefficient times wL4/EI for a uniform load and times PL3/EI for a point load:
| Case | Uniform load w | Point load P at mid-span (cantilever: at the tip) |
|---|---|---|
| Simply supported | 5wL4/384EI | PL3/48EI |
| Cantilever | wL4/8EI | PL3/3EI |
| Fixed at one end, pinned at the other | wL4/185EI | PL3/(48√5 EI) |
| Fixed at both ends | wL4/384EI | PL3/192EI |
The same uniform load on the same span deflects a fixed-ended beam five times less than a simply supported one, and a cantilever of the same length almost ten times more. That is why the support assumption matters as much as the section; the guide on choosing support conditions looks at it in detail.
Worked example: a steel floor beam
Take the numbers of the free simple beam calculator: span L = 6 m, uniform load w = 20 kN/m, E = 200 000 MPa and I = 8000 cm⁴.
If the 20 kN/m is the total load, the limit span/240 = 25 mm is met. If the same 20 kN/m were live load alone, span/360 = 16.7 mm would not be met: the beam would need a moment of inertia of at least 8000 × 21.1 / 16.7 ≈ 10 100 cm⁴, because deflection is inversely proportional to I.
The same example also shows why both checks are needed: the bending stress M/S = 90 kN·m / 500 cm³ = 180 MPa exceeds an allowable stress of 165 MPa, so this section fails in strength before deflection is even considered.
Practical tips
- Span first. Deflection is proportional to L4: a span 10 % longer deflects about 46 % more. An intermediate support or a shorter span is often the cheapest fix.
- Depth second. For a rectangular section I grows with the cube of the depth, so a section 26 % deeper halves the deflection.
- Use consistent units. Most hand-calculation errors in deflection are unit errors: kN/m with mm, or cm⁴ with m. Converting everything to N and mm before substituting avoids them.
- Deflection is not vibration. A floor can meet span/360 and still feel lively. Long steel and timber floors need a separate vibration check based on natural frequency.
- Precamber is an option for long steel beams: it hides the dead-load deflection, but it does not reduce the live-load deflection that finishes see.