Propped Cantilever Beam — Concentrated Load at Center

Propped Cantilever · Concentrated Load at Center · AWC Design Aid No. 6 — Figure 16
Worked example

This page shows the complete calculation with example values: the inputs, the results and every step in between.

The interactive calculator is part of HandCalc Pro. With Pro you can enter your own values, switch between SI and Imperial units and download the technical report as PDF or Word.

1

Geometry and load

Span and concentrated load at midspan (fixed on the left, pinned on the right)
m
kN
2

Show calculation details

RA, RB, MA, Mmax+
RAat the fixed end = 11P16 = 27.50kN
RBat the roller support = 5P16 = 12.50kN
MAfixed-end moment = 3Pℓ16 = 45.00kN·m
Mmax+at x = ℓ/2 = 5Pℓ32 = 37.50kN·m
M = 0inflection point @ x = 3ℓ/11 = 1.636m
3

Deflection calculation

Define E and I for δmax
MPa
cm⁴
δmaxat x ≈ 0.553ℓ = 5.03mm
δ(x) = Px²(9ℓ − 11x)96 EI  (x ≤ ℓ/2)
δ(x) = P[9ℓx²−11x³+16(x−ℓ/2)³]96 EI  (x > ℓ/2)
Deflected Shape Diagram
δₘₐₓ = 5.03 mm3.33 mm
4

Bending-stress check

Compare σmax against the allowable stress
cm³
MPa
σmax = MmaxS = 45 × 10³500 = 90.00MPa

Mmax is taken as the larger of |MA| and Mmax+.

0.55 σ / Fb
Safe
5

Point analysis

Vx, Mx, δx at a given point x
m
0 (fixed) ℓ/2 = 3 m 6 m
Vx = RA  (x < ℓ/2)  /  −RB  (x > ℓ/2) = 27.50kN
Mx = −3×40×6/16 + 11×40×2/16 = 10.00kN·m
δx = 3.33mm